Edison ECNR60 ECNR Current Limiting Time Delay Fuse, 60 A, 250 V AC/125 V DC, 200 kAIC Interrupt, Class: RK5, Cylindrical Body
Edison's UL Class RK5 dual-element, time-delay fuses provide economical solutions to overcurrent protectioni. Available in both 250Vac and 600Vac, with 200kA RMS Sym interrupting ratings and sizes ranging from 0 to 600 amp.
-
BrandEdison
-
UPC782634507390
-
Manufacturer Part NumberECNR60
-
CountryUSA
-
Terminal TypeFerrule End
-
MaterialFiberglass
-
ClassRK5
-
Rejection/Non-RejectionRejection
-
Response Time10 s at 500%
-
TypeCurrent Limiting Time Delay
-
Voltage Rating250 V AC/125 V DC
-
Amperage Rating60 A
-
SeriesECNR
-
Indicating/Non-IndicatingNon-Indicating
-
Interrupt Rating200 kAIC
-
Body Size0.81 in Dia x 3 in L
-
Body TypeCylindrical
-
ElementDual
- Provides motor overload, ground fault and short circuit protection
- Helps protect motors against burnout from 1 ph on 3 ph systems
- Simplifies and improves blackout prevention (selective co-ordination ratios)
- Dual element fuses can be applied in circuits subject to temporary motor overloads and surge currents to provide both high performance short circuit and overload protection
- The overload element provides protection against low level overcurrent of overloads and will hold an overload which is 5X greater than the amperage rating of the fuse for a minimum of 10 s
- Superior overload and cycling capabilities
- True dual element construction allows sizing of 125% FLA for motor backup protection
- Current limiting provides component short circuit protection
- For all general purpose applications including lighting, heating and other non-inductive loads
- Tin plated copper brass terminal and zinc plated steel screws
| Competitor Name | Competitor Part Number |
|---|---|
| Grainger | 12W260 |
-
Alternative Part Number11197139|13663990
-
UNSPSC39121606
-
IDEA Index ID11197139
-
Package DescriptionEACH
-
Standards/ApprovalsCE Certified|CSA C22.2 File No.700489/248.12|UL 248-12 File No.E162363 Guide JDDZ
-
Specification Sheet
-
Owners/User Manual
Recently Viewed
Edison ECNR60 ECNR Current Limiting Time Delay Fuse, 60 A, 250 V AC/125 V DC, 200 kAIC Interrupt, Class: RK5, Cylindrical Body
Edison's UL Class RK5 dual-element, time-delay fuses provide economical solutions to overcurrent protectioni. Available in both 250Vac and 600Vac, with 200kA RMS Sym interrupting ratings and sizes ranging from 0 to 600 amp.
Edison ECSR10 ECSR Current Limiting Time Delay Fuse, 10 A, 600 V, 200 kAIC Interrupt, Class: RK5, Cartridge Body
Edison's UL Class RK5 dual-element, time-delay fuses provide economical solutions to overcurrent protectioni. Available in both 250Vac and 600Vac, with 200kA RMS Sym interrupting ratings and sizes ranging from 0 to 600 amp.
Appleton® ETP⢠8469A Raised Square Box Cover, 4 in L x 4 in W x 1 in D, Steel
Appleton® ETP⢠8469A Raised Square Box Cover, 4 in L x 4 in W x 1 in D, Steel
Gardner Bender 10-410C Crimp Connector, 18 to 10 AWG Copper Wire, Steel
The JCASE⢠is a cartridge style fuse with female terminal design, providing both increased time delay and low voltage drop to protect high current circuits and handle inrush currents. The JCASE⢠was designed and patented by Littelfuse.
Edison ECNR40 ECNR Current Limiting Time Delay Fuse, 40 A, 250 V AC/125 V DC, 200 kAIC Interrupt, Class: RK5, Cylindrical Body
Edison's UL Class RK5 dual-element, time-delay fuses provide economical solutions to overcurrent protectioni. Available in both 250Vac and 600Vac, with 200kA RMS Sym interrupting ratings and sizes ranging from 0 to 600 amp.