Edison JDL35 Time Delay Fuse, 35 A, 600 V AC, 200 kA Interrupt, J Class
Edison's UL Class J fuse products are offered in both Dual-Element Time-Delay (JDL) and Fast-Acting (JFL) types. Both types have 200,000 amp interrupting rating at 600Vac RMS Sym amps. Their small physical size and high performance characteristics makes Class J fuses ideal for any space-limited applications. Edison's JFL fuses are best suited for the protection of non-inductive loads such as resistive heating and lighting circuits.
-
BrandEdison
-
UPC782634803416
-
Manufacturer Part NumberJDL35
-
CountryUSA
-
ClassJ
-
Voltage Rating600 V AC
-
Amperage Rating35 A
-
SeriesJDL
-
Interrupt Rating200 kA
-
Body Size1.06 in Dia x 2.38 in L
-
ElementDual
- True dual-element fuses with a minimum 10 s time delay at 500% overload
- Long time delay minimizes needless fuse openings due to temporary overloads and transient surges
- Can often be sized for back-up protection against motor burnout from overload or single-phasing if other overload protective devices fail
- High interrupting rating to safely interrupt overcurrent's up to 300 kA (self certified)
- High degree of current-limitation due to the fast speed-of-response to short-circuits
- Faster response to damaging short-circuit currents than mechanical overcurrent protective devices
- Reduces let-through thermal and magnetic forces in order to protect low withstand rated components
- Proper sizing provides no damage type 2 coordinated protection for NEMA and IEC motor control in accordance with IEC standard 947-4-1
- Dual-element fuses have lower resistance than ordinary fuses so they run cooler
- Lower watts loss reduces power consumption
- Unique dimensions assure that another class of fuse with a lesser voltage rating, interrupting rating or current-limiting ability cannot be substituted
- Space-saving package for equipment down sizing
- Use to protect lower interrupting rating circuit breakers, type 2 no damage protection of IEC style motor starters and contactors
-
Alternative Part Number8430335
-
UNSPSC39121626
-
IDEA Index ID8430335
-
Package DescriptionEACH
-
Standards/ApprovalsBAA Compliant|CE Certified|CSA Certified|HRCI-J 200,000 AIR, Class J per CSA 22.2 No 248.8, Class 1422-02, File 53787|UL Class J, Guide JDDZ, File E162363
-
Specification Sheet
Recently Viewed
Edison's UL Class J fuse products are offered in both Dual-Element Time-Delay (JDL) and Fast-Acting (JFL) types. Both types have 200,000 amp interrupting rating at 600Vac RMS Sym amps. Their small physical size and high performance characteristics makes Class J fuses ideal for any space-limited applications. Edison's JFL fuses are best suited for the protection of non-inductive loads such as resistive heating and lighting circuits.
75-WATT HARD-SHELL FLOODLIGHT BULBS
Browning 17-TOOTH #60-1 CHAIN SPROCKETS BRW H-6017 X 1-1/4
BrowningĀ® finished bore sprockets are offered in single strands. Offerings include 35 to 100 pitch range. Finished bore sprockets are available from 3/8 to 2-7/16 in. Hardened teeth are available up to 30 teeth.
MORSEĀ® 14625 1396 1-Stage Type A Heavy Duty Jobber Length Aircraft Drill, #20 Drill - Wire, 0.161 in Drill - Decimal Inch, 118 deg Point, HSS
MORSEĀ® 14625 1396 1-Stage Type A Heavy Duty Jobber Length Aircraft Drill, #20 Drill - Wire, 0.161 in Drill - Decimal Inch, 118 deg Point, HSS
EklindĀ® 51606 Hex Key, Hex Drive, Cushion Loop T-Handle Handle, Alloy Steel, Black Oxide
EklindĀ® 51606 Hex Key, Hex Drive, Cushion Grip/Loop T-Handle Handle, Alloy Steel, Black Oxide
LittelfuseĀ® POWR-GARDĀ® FLNR090 FLNR Current Limiting Time Delay Fuse, 90 A, 250 V AC/125 V DC, 200/20 kA Interrupt, RK5 Class, Cylindrical Body
LittelfuseĀ® FLNR series fuses have been the superior UL Class RK5 dual element time delay fuses and are the most widely used Class of fuses. FLNR series fuses provide excellent protection for all types of circuits especially those containing motors. However, users and specifiers should consider the significant benefits offered by indicator fuses.