Edison JDL35 Time Delay Fuse, 35 A, 600 V AC, 200 kA Interrupt, J Class
Edison's UL Class J fuse products are offered in both Dual-Element Time-Delay (JDL) and Fast-Acting (JFL) types. Both types have 200,000 amp interrupting rating at 600Vac RMS Sym amps. Their small physical size and high performance characteristics makes Class J fuses ideal for any space-limited applications. Edison's JFL fuses are best suited for the protection of non-inductive loads such as resistive heating and lighting circuits.
-
BrandEdison
-
UPC782634803416
-
Manufacturer Part NumberJDL35
-
CountryUSA
-
ClassJ
-
Voltage Rating600 V AC
-
Amperage Rating35 A
-
SeriesJDL
-
Interrupt Rating200 kA
-
Body Size1.06 in Dia x 2.38 in L
-
ElementDual
- True dual-element fuses with a minimum 10 s time delay at 500% overload
- Long time delay minimizes needless fuse openings due to temporary overloads and transient surges
- Can often be sized for back-up protection against motor burnout from overload or single-phasing if other overload protective devices fail
- High interrupting rating to safely interrupt overcurrent's up to 300 kA (self certified)
- High degree of current-limitation due to the fast speed-of-response to short-circuits
- Faster response to damaging short-circuit currents than mechanical overcurrent protective devices
- Reduces let-through thermal and magnetic forces in order to protect low withstand rated components
- Proper sizing provides no damage type 2 coordinated protection for NEMA and IEC motor control in accordance with IEC standard 947-4-1
- Dual-element fuses have lower resistance than ordinary fuses so they run cooler
- Lower watts loss reduces power consumption
- Unique dimensions assure that another class of fuse with a lesser voltage rating, interrupting rating or current-limiting ability cannot be substituted
- Space-saving package for equipment down sizing
- Use to protect lower interrupting rating circuit breakers, type 2 no damage protection of IEC style motor starters and contactors
-
Alternative Part Number8430335
-
UNSPSC39121626
-
IDEA Index ID8430335
-
Package DescriptionEACH
-
Standards/ApprovalsBAA Compliant|CE Certified|CSA Certified|HRCI-J 200,000 AIR, Class J per CSA 22.2 No 248.8, Class 1422-02, File 53787|UL Class J, Guide JDDZ, File E162363
-
Specification Sheet
Recently Viewed
Edison's UL Class J fuse products are offered in both Dual-Element Time-Delay (JDL) and Fast-Acting (JFL) types. Both types have 200,000 amp interrupting rating at 600Vac RMS Sym amps. Their small physical size and high performance characteristics makes Class J fuses ideal for any space-limited applications. Edison's JFL fuses are best suited for the protection of non-inductive loads such as resistive heating and lighting circuits.
GE SEALED BEAMS 4340 WAE-KW-3506003 >
5/8" BRASS SHORT FLARE NUTS-JWH441821>
5" 2-PIECE CLAMP SHAFT COLLAR
THE BLACK DIGITAL RG6 COAXIAL CABLE WITH F CONNECTOR IS A QUALITY CABLE THAT CAN BE USED WITH AN ANTENNA, VCR, TV, CABLE BOX, OR SATELLITE RECEIVER. THE CABLE CARRIES BOTH AUDIO AND VIDEO SIGNALS
JWH502790>
LittelfuseĀ® POWR-GARDĀ® JLS100 High Speed Fast Acting Fuse, 100 A, 600 V AC, 200 kA Interrupt, J Class, Cartridge Body
JLS series fuses provide space-saving, fast acting overload and short circuit protection for non-inductive loads. When used for motors or other inductive loads, the ampere rating of JLS series fuses must be increased to prevent nuisance opening on inrush currents. In such applications, JLS fuses may provide only short circuit protection.